BECCO2200 DCA
Configuration Guide
GE Energy Services
Restricted A164-0CG-1.00-2
Full
27
F105: Invalid SOE Overflow parameter
Cause:
• The SOE Buffer Overflow Option configuration parameter in the A164APPL table is neither
Overwrite Oldest (0) nor Discard Newest (1).
Remedy:
• ·Review the section on configuring the A164APPL table (Chapter 3:) and verify that the
SOE Buffer Overflow Option is configured correctly.
F106: Total # devices exceeds UNIT size
Cause:
• The sum of all BECO2200 devices specified in all records of the A164PORT table is greater
than the number of records in the A164UNIT table.
Remedy:
• Address all fatal and non-fatal error messages preceding this message.
• Review the section on configuring the A164PORT table (Chapter 4:) and verify that the
Number of Devices on Port configuration parameter in each record is correct.
• Verify the sum of all Number of Devices on Port configuration parameters is less than or
equal to the number of records in the A164UNIT table.
F107: <x> WESDAC_<y> pnts configured, <z> required
Cause:
• <x> number of WESDAC_<y> points were configured in the WIN CFG_DCA table for the
BECO2200 DCA. <z> points are required.
Remedy:
• Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:) and verify
that the number of WESDAC_<y> points configured for the BECO2200 DCA is greater than
or equal to <z>.
WESDAC NUMBER DATA TYPE
WESDAC_1 Binary Input
WESDAC_2 Binary Output
WESDAC_3 Counter
WESDAC_4 Analog Input
WESDAC_5 Analog Output
WESDAC_6 Device Status
Table 10 WESDAC Number Definitions