F105: Invalid SOE Overflow parameter
Cause:
The SOE Buffer Overflow Option configuration parameter in the A164APPL table is neither
Overwrite Oldest (0) nor Discard Newest (1).
Remedy:
·Review the section on configuring the A164APPL table (Chapter 3:) and verify that the
SOE Buffer Overflow Option is configured correctly.
F106: Total # devices exceeds UNIT size
Cause:
The sum of all BECO2200 devices specified in all records of the A164PORT table is greater
than the number of records in the A164UNIT table.
Remedy:
Address all fatal and non-fatal error messages preceding this message.
Review the section on configuring the A164PORT table (Chapter 4:) and verify that the
Number of Devices on Port configuration parameter in each record is correct.
Verify the sum of all Number of Devices on Port configuration parameters is less than or
equal to the number of records in the A164UNIT table.
F107: <x> WESDAC_<y> pnts configured, <z> required
Cause:
<x> number of WESDAC_<y> points were configured in the WIN CFG_DCA table for the
BECO2200 DCA. <z> points are required.
Remedy:
Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:) and verify
that the number of WESDAC_<y> points configured for the BECO2200 DCA is greater than
or equal to <z>.
WESDAC NUMBER DATA TYPE
WESDAC_1 Binary Input
WESDAC_2 Binary Output
WESDAC_3 Counter
WESDAC_4 Analog Input
WESDAC_5 Analog Output
WESDAC_6 Device Status
Table 10 WESDAC Number Definitions