GE BECCO2200 Webcam User Manual


 
GE Energy Services
BECCO2200 DCA
Configuration Guide
A164-0CG-1.00-2 Restricted
12
Full
4.2.8 Line Idle Time
This parameter specifies the minimum time, in milliseconds, that the communication line should
remain idle between the end of a response from a BECO2200 device and the beginning of the
next transmission from the BECO2200 DCA.
4.2.9 Retries Before Failure
This parameter specifies the number of automatic retries that can be conducted by the
BECO2200 DCA on a single transaction (scan/response). For every given transaction, the scan
can be retried this number of times in the event of a data link error. If no response is received
that passes the data link error check within the number of retries configured, the transaction is
considered failed.
4.2.10 Failures Before Off-line
This parameter specifies the number of consecutive transactions that must fail before a
BECO2200 device is considered off-line.
4.2.11 Number of Devices on Port
This parameter specifies the number of devices to communicate on this port. This is configured
as a range of records in the A164PORT table. For example, if the first A164PORT record has
four devices and the second A164PORT record has three devices, the first four devices
configured in the A164PORT table will communicate on the first port, and the next three
devices configured in the A164UNIT table will communicate on the second port.