BECCO2200 DCA
Configuration Guide
GE Energy Services
Restricted A164-0CG-1.00-2
Full
33
E303: PORT rec <x>, configuration bad
Cause:
• The BECO2200 DCA encounter non-fatal errors in record <x> of the A164PORT table.
Effect:
• Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
• Address all non-fatal errors preceding this message.
E304: PORT rec <x>, invalid unit address
Cause:
• Record <x> of the A164PORT table contains an invalid Unit Address.
Effect:
• Communication to all BECO2200 devices configured to use this port will be unavailable.
Remedy:
• Review the section on configuring the A164PORT table (Chapter 4:), and verify that the
Unit Address configuration parameter is within the range of 0 through 255.
E305: UNIT rec <x>, invalid unit type
Cause:
• Record <x> of the A164UNIT table contains an invalid Unit Type.
Effect:
• Communication to this unit will be unavailable.
Remedy:
• Review the section on configuring the BECO2200 DCA A164UNIT Configuration Table
(Chapter 5:), and verify that the Unit Type is BECO2200-M-0420 (0)
E306: Unit <x> and <y>, same address on port <z>
Cause:
• Two BECO2200 devices have been configured with the same address on port <z>.
Effect:
• Communication to the two devices will be unavailable.
Remedy:
• Review the section on configuring the A164UNIT table (Chapter 5:), and verify that the
addresses of records <x> and <y>. Each unit address on a given port must be unique.
E307: UNIT rec <x>, configuration bad
Cause:
• The BECO2200 DCA encountered non-fatal errors in record <x> of the A164UNIT table.
Effect:
• Communication to this unit will be unavailable.