F100: Bad A164APPL record counts, must be 1
Cause:
The A164APPL configuration table contained a number of records not equal to one.
Remedy:
Review the section on configuring the A164APPL table (Chapter 3:), and ensure that the
table consists of only one record.
F101: Bad A164PORT record counts, must be > 0
Cause:
The A164PORT configuration table contained a number of records less than one.
Remedy:
Review the section on configuring the A164PORT (Chapter 4:), and ensure that the table
consists of one or more records.
F102: Bad A164UNIT record counts, must be > 0
Cause:
The A164UNIT contained a number of records less than one.
Remedy:
Review the section on configuring the A164UNIT (Chapter 5:), and ensure that the table
consists of one or more records.
F103: Bad CFG_DCA record counts, must be > 0
Cause:
The CFG_DCA configuration table contained a number of records less than one.
Remedy:
Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:), and ensure
that the table consists of one record for every DCA and DTA in the system.
Review the WIN User’s Configuration Guide for more information on how to configure
WIN.
F104: Invalid DCA index
Cause:
The DCA Index configuration parameter in the A164APPL table specifies an invalid index
into the WIN CFG_DCA table.
Remedy:
Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:), and ensure
that the table consists of one record for every DCA and DTA in the system.
Review the section on configuring the A164APPL table (Chapter 3:) and verify that the
DCA Index parameter specifies a valid index into the WIN CFG_DCA table (the index is a
zero based table offset).