GE Energy Services
BECCO2200 DCA
Configuration Guide
A164-0CG-1.00-2 Restricted
26
Full
F100: Bad A164APPL record counts, must be 1
Cause:
• The A164APPL configuration table contained a number of records not equal to one.
Remedy:
• Review the section on configuring the A164APPL table (Chapter 3:), and ensure that the
table consists of only one record.
F101: Bad A164PORT record counts, must be > 0
Cause:
• The A164PORT configuration table contained a number of records less than one.
Remedy:
• Review the section on configuring the A164PORT (Chapter 4:), and ensure that the table
consists of one or more records.
F102: Bad A164UNIT record counts, must be > 0
Cause:
• The A164UNIT contained a number of records less than one.
Remedy:
• Review the section on configuring the A164UNIT (Chapter 5:), and ensure that the table
consists of one or more records.
F103: Bad CFG_DCA record counts, must be > 0
Cause:
• The CFG_DCA configuration table contained a number of records less than one.
Remedy:
• Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:), and ensure
that the table consists of one record for every DCA and DTA in the system.
• Review the WIN User’s Configuration Guide for more information on how to configure
WIN.
F104: Invalid DCA index
Cause:
• The DCA Index configuration parameter in the A164APPL table specifies an invalid index
into the WIN CFG_DCA table.
Remedy:
• Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:), and ensure
that the table consists of one record for every DCA and DTA in the system.
• Review the section on configuring the A164APPL table (Chapter 3:) and verify that the
DCA Index parameter specifies a valid index into the WIN CFG_DCA table (the index is a
zero based table offset).