F108: <x> table creation error
Cause:
The BECO2200 DCA tried to create the <x> table in RAM, and it failed.
Remedy:
Reduce the amount of RAM used by this and any other application residing in the system.
Parameters that affect the amount of RAM used by this application are noted in their
associated chapters.
Upgrade the GE Energy Services product to a model with more memory.
Call the Customer Service department and report this error.
F109: Cannot find <x> database table
Cause:
The BECO2200 DCA requires a number of points of a certain WESDAC point type, but
cannot find the associated table, <x>.
Remedy:
Review the section on configuring WIN for the BECO2200 DCA (Chapter 2:) and verify
that there are points of type <x> configured in one or more of the CFG_DCA records.
Call the Customer Service department and report this error.
F110: Fatal errors exist in configuration
Cause:
The BECO2200 DCA encountered fatal errors in the configuration.
Remedy:
Address all fatal error messages preceding this message.
F111: Bad A164DVCF record counts, must be > 0
Cause:
The A164DVCF configuration table contained a number of records less than one.
Remedy:
Review the section on configuring the A164DVCF table (Chapter 7:), and ensure that the
table consists of at least zero records.
F112: Bad A164DTBL record counts, must be > 0
Cause:
The A164DTBL configuration table contained a number of records less than one.
Remedy:
Review the section on configuring the A164DTBL table (Chapter 8:), and ensure that the
table consists of one or more records.