F 2 4 High Limiter
F 2 5 Low Limiter
The upper and lower and lower limits of the output frequency can be set.
0
Set as a percentage of the maximum frequency in increments of 1% within a range of 0 to 100%
100
If the value set for low limiter is higher than that set for the
high limiter, the high limiter will take priority and the low
limiter will be ignored. Thus, operation will always be in
accordance with the high limiter value regardless of the
frequency setting.
F 2 6 Bias Frequency
Outputs a bias frequency with respect to the analog frequency setting.
0
Set as a percentage of the maximum frequency in increments of 1% within a range of 0 to 100%
100
F 2 7 THR Terminal Function
This function enables terminal THR to be used for two different functions by changing the data
code as follows:
0
External alarm input
1
Multistep speed selection (X1)
This function data cannot be changed during operation. (Possible to change only in STOP mode).
F 2 8 BX Terminal Function
This function enables terminal BX to be used for two different functions by changing the data code as follows:
0
Motor coast-to-stop command input
1
Multistep speed selection (X2)
This function data cannot be changed during operation. (Possible to change only in STOP mode).
100%
100%
High
limiter
Output
frequency
Low limiter
Frequency
setting
100%
100%
Output
frequency
Frequency
setting
Bias