6) It is important that all lead length are kept
as short as possible and that incoming
mains and outgoing motor cables are kept
well separated.
7) Segregate power cables from control
wiring as possible as you can, and avoid
parallel cable runs to minimize “noise cou-
pling”. Wherever runs of power and control
cable must cross, try to achieve this at right
angles.
8) FVR drives should be installed, and are
designed to operate, within an electrically
shielded metal enclosure.
The RFI filters range are designed especially
for the FVR drive and help to ensure EMC
compliance of machinery an installations
using the drives. The drives may be mounted
on top of the filter using the integral fixing
positions, the intention being that valuable
space inside wiring cabinets may be saved.
(Refer to Fig. 1 and Table 1)
Filter Applied Rated Max Rated Dimensions inches Drive Sub
Part No. Drive Current Voltage L x W x H X Y Fixings Filters
EFL-0.2C9-7 FVRF12C9S-7UX 3A 6.69 x 3.35 x 1.38 1.97 6.1 M4 0.16 Ferrite
FVRF25C9S-7UX x0.63 (2pcs.) OC1x (1 pcs.)
EFL-0.75C9-7 FVRF50C9S-7UX 10A 1-Phase 6.69 x 3.35 x 1.38 1.97 6.10 M4 0.16
FVR001C9S-7UX 240 VAC x0.63 (2 pcs.)
EFL-2.2C9-7 FVR002C9S-7UX 16A 7.09 x 4.53 x 1.38 3.50 6.50 M4 0.16 Ferrite
x0.63 (4 pcs.) OC2x (1 pcs.)
7-'006
Mains input
terminals
Earth Stud
Drive fixing
positions
Earth Stud
Load terminals
to drive
input
Y
X
W
L
N
LINE
LOAD
L’
N’
L
H
Fig. 1 RFI Filters
Table 1 RFI Filter Dimensions Conforms to EN55011 Class B