GE FVR-C9S-7UX Power Supply User Manual


 
6
FVR-C9S-7UX
1. Inspection Upon Receipt
Please inspect the following items upon receipt
of your drive.
• Check the name plate to insure the specifica-
tions correspond to those ordered.
• Inspect the unit for damage which may have
occurred during shipping.
If you have any problems or questions regarding
the drive, please contact the nearest Fuji sales
office or the distributor where the unit was
purchased.
Nameplate
UL/CSA
WARNING / AVERTISSEMENT
Hazard of electrical shock. Disconnect incoming
power before working on this control.
Risque de choc electrique. Couper l’alimentation
avant le depannage de sette commande.
More than one live circuit. See diagram. Cet
equipment renferme plusieurs circuits sous
tension. Voir le schema
CAUTION ATTENTION
Dangerous voltage exists until charge light is off.
Prede tensions dangereuses tant que le voyant
n’est pas eteint.
Suitable for use on a circuit capable of delivering
not more than 5,000 rms symmetrical amperes.
240V maximum.
• Use 60/75° C copper wire only.
• Use Class 1 wire only.
• Open type equipment
• Tightening torque and wire range for field
␣ ␣ ␣ wiring terminals are as follows:
Model Required Wire
torque (N.m) range
FVRF12C9S-7UX 0.98 14
FVRF25C9S-7UX 0.98 14
FVRF50C9S-7UX 0.98 14
FVR001C9S-7UX 0.98 14
FVR002C9S-7UX 0.98 14
Control board
terminal 0.7 24
Use the listed quick-acting fuse in series. Fac-
tory recommendation is a Bussman type JKS or
equivalent. Fuses are required to validate the UL
and CSA listings.
Model Dist. fuse size,600V
FVRF12C9S-7UX 20
FVRF25C9S-7UX 20
FVRF50C9S-7UX 20
FVR001C9S-7UX 20
FVR002C9S-7UX 30
Field wiring connection shall be made by a UL
listed and CSA Certified closed-loop terminal
connector sized for the wire gauge involved.
Connector must be fixed using the crimp tool
specified by the connector manufacturer.
OTHER
WARNING:
FIRE AND PERSONAL INJURY HAZARD
Do not carry out any modifications to the drive.
Doing so may result in electric shock and injury.
GENERAL CAUTION
All of the illustrations in this instruction manual
show the drive with the covers and other protec-
tive equipment removed in order to facilitate
explanation of detailed parts of the drive. Be
absolutely sure to return all covers and protective
equipment to the prescribed positions before
operating the drive, and make sure that all opera-
tions are carried out in accordance with the
instructions in this manual.
TYPE
SOURCE
OUTPUT
SER. NO.
FVRF 12C9S-7UX
1PH 200-240V 1.7A 50/60 HZ
3PH 200-230 0.66A 1/8HP 1-120HZ
Fuji Electric Co. Inc. Japan
1
2 3 4
5 6 7
8