ICP DAS USA 100-700 PLCS Switch User Manual


 
DeviceNet to Motor Drives
35
INPUT DATA TABLE
Within the “I/O Data Configuration” screen, use the DOWN arrow key to move the focus to the Input
Data button and press the ENTER key. This action opens the Input Data Table setup screen to allow you
to set up the motor drive parameters to be mapped to each word of Input data.
Input data is data read from motor drive parameters and sent from the DN-3000 to the DeviceNet Host.
Each word of Input data (except those reserved for the Command Block and Diagnostics) can be mapped
to specific motor drive parameters. Mapped motor drive parameters in the Input Data Table are read from
the motor drives and placed in the Input data in a round-robin fashion as quickly as the motor drives’
serial communications link allows.
Use the UP/DOWN arrow keys to scroll through the list of Input data words until the highlight bar is over
the Input word you wish to edit, and press ENTER. A window will open allowing you to edit the Motor
Drive Address and Parameter Number mapped to that Input word.