Operation
24
Status/Alarm Message Areas
The status/alarm message areas display vital information about the operation of the UPS system.
During normal operation no alarm messages should be present. Changes in the status of the system
and possible alarm conditions can be monitored. Both the status and the alarm messages are dis-
played in reverse video (highlighted—light on dark). The alarm messages continue flashing until the
Horn Off pad is pressed. To clear a latching alarm, you must also press the Alarm Reset pad after
the alarm condition is corrected.
The following lists show the status and alarm messages that may be displayed in these areas. For
more information and the corrective actions for these messages, refer to Table 4 in this section.
Item 6 - Status Messages
Static Switch Connected
Static Switch Disconnected
OK To Transfer
Not OK To Transfer
Item 7 - Alarm Messages
Figures 8 through 11 illustrate how the Monitor/Mimic Display screens depict the power flow
through the UPS.
Figure 8 Monitor/Mimic display example: Normal power flow
Input Fail Output Over/Underfrequency
DC Ground Fault Output Undervoltage
DC Capacitor Fuse Blown Output Overvoltage
Battery CB Open Overload
Battery Discharging Overload Transfer
Low Battery Warning Inverter Non-Sync
Low Battery Shutdown Reverse Power
DC Overvoltage Shutdown Rectifier Fuse Blown
Load On Bypass Inverter Fault
Auto Retransfer Primed Hardware Shutdown
Manual Reset/Retransfer Emergency Off
Static Switch Unable Battery Cycle Buffer Warning
Bypass Not Available Ambient Overtemperature
Bypass Phase Sequence Wrong Blower Failed
Control Power Fail Equipment Overtemperature
Battery Overtemp Overtemperature Time-out
Battery Exercise
UPS INPUT PWR
480V 480V 480V
350A 350A 350A
BATTERY
VOLTS 540
AMPS 15 CHARG
UPS RATINGS
A-B B-C C-A
480V 480V 480V
60.0 Hz
AP658-64
RATED 500 KVA
OUTPUT VOLTAGE
BYPASS INPUT
A-B B-C C-A
480V 480V 480V
60.0 Hz
LOAD
A B C
270 KVA / 217 KW
325A 325A 325A
A-B B-C C-A
OK to Transfer
Static Switch Connected
© 1989-2003