3.3.6 Emergency Module Off
The Local Emergency Module Off (LEMO) mode is used to remove power from nearly all UPS module
components, and the critical load will continue to be supplied through the bypass line.
The Emergency Module Off control is a guarded pad on the UPS Control Panel (Figure 4).
Lift the cover and press the pad. The load will be transferred to bypass, and the battery (MBD), input
and output circuit breakers will be opened (tripped). This will remove power from all UPS module
components except the controls, bypass circuit breaker and the static switch.
Refer to 3.4.4 - Shutdown Procedures.