Liebert 610 Power Supply User Manual


 
Operation
77
STEP 3 (Shutdown Procedures)
Manually open the UPS input circuit breaker by moving the handle to the OFF position (Figure 3).
Return to the Monitor/Mimic Display to verify status of the circuit breakers. Press the Alarm Reset
pad to clear alarm messages.
STEP 4 (Shutdown Procedures)
If maintenance is required on the Static Bypass Switch, open the two Static Disconnect fusehold-
ers.
STEP 5 (Shutdown Procedures)
If maintenance is required on the UPS controls, open the Control Disconnect fuseholders and open the
Rectifier Input Breaker (RIB), external to the UPS cabinet.
At this point, power is removed from the UPS module components, but the bypass line is still ener-
gized and supplying power to the load.
STEP 6 (Shutdown Procedures)
If maintenance is required in the area of the UPS motorized circuit breakers, transfer the load to the
Maintenance Bypass, if available (refer to 3.4.3 - Maintenance Bypass Load Transfers).
Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARNINGS
in 4.0 - Maintenance.
Local Emergency Modules Off (LEMO)
The UPS controls include an Emergency Module Off pad (Figure 3, item 13). When this guarded
pad is pressed, the load is automatically transferred to the bypass line and the module output, battery
and input circuit breakers trip open to isolate and shut down and isolate the UPS module. Control
Power for indicators and alarms remains On.
Remote Emergency Power Off (REPO)
The Remote Emergency Power Off control (REPO) is a switch located remotely from the UPS system.
It will normally be in the same room as the critical load equipment.
The Remote Emergency Power Off switch removes all power to the critical load.
When you trip the Remote Emergency Power Off switch, all UPS circuit breakers are opened, includ-
ing the bypass circuit breaker. All power through the UPS is removed from the load. You will still
have power to the UPS controls, and you may have power to the static switch.
!
CAUTION
The UPS bypass line is still energized.
!
CAUTION
If your installation does not include a Maintenance Bypass, power must still be isolated from
both sides of the UPS circuit breakers if maintenance is required. This will result in loss of
power to the critical load. Perform an orderly load shutdown before isolating power.
!
WARNING
Lethal voltages are present within this unit even when it is not on or when utility is not being
supplied. Observe all cautions and warnings in this manual. Failure to do so could result in
serious injury or death. Do not work on or operate this equipment unless you are fully
qualified to do so! Never work alone.