Liebert 610 Power Supply User Manual


 
Maintenance
90
If you have a different model battery, contact Liebert Global Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once
disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.
The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and
insulate the cables connected to the battery. Secure each battery shelf with retaining screws when
maintenance is complete.
Rack-Mounted Batteries
If the UPS system uses a battery other than a factory-supplied Matching Battery Cabinet, perform
maintenance on the battery as recommended in the battery manufacturer’s maintenance manual,
available on the manufacturer’s Web site.
Table 8 Battery retorque values
Battery
Manufacturer
Battery
Model No.
Retorque
Value
Dynasty
UPS12
-270(FR) 32 lb-in.
UPS12
-310(FR) 52 lb-in.
UPS12
-370(FR) 52 lb-in.
UPS12
-475(FR) 100 lb-in.
C&D Batteries
LS12
-100 100 lb-in.
12G
-17 100 lb-in.
Enersys
HX205 60 lb
-in.
HX300 60 lb
-in.
HX370 60 lb
-in.
HX400 60 lb
-in.
HX500 60 lb
-in.
Table 9 Battery voltage record
Date Float Voltage (Volts DC) Nominal Voltage (Volts DC) Ambient Temp. (°F)
(To be completed by Liebert Global Services customer engineer at time of start-up)