Operation 47
Active Cycle Time in place of Accumulated Battery Time, and shows Active Battery AH and Active Battery
kWH instead of accumulated values.
Figure 27 Battery Cycle Monitoring Summary Screen
Figure 28 shows a typical detail screen for the 91-240 Seconds Discharge category. This information can be col-
lected remotely, through the optional communications board and modem, by a remote terminal or a personal
computer equipped with a modem and communications program. See 3.1.14 - Communication Interfaces for
more information.
Figure 28 Typical Data on Discharge Cycles of 91 to 240 Seconds Duration During the Recording
Period
NOTE
This information is applicable to systems with separate batteries for each module. If
the modules share a common battery, select one module to do the monitoring and
disregard the other(s).
7
15 min. 32 sec.
71
34
25°C / 77°F
TotalNo.ofCycles.............
AccumulatedBatteryTime.......
AccumulatedBatteryAH........
AccumulatedBatteryKWH.......
BatteryTemperature............
Battery Cycle MonitoringSummary
EXITSELECT :
EXIT
Event Date Time Duration Min. Volt Max. Amp Start KW Start Temp
15 4/12/95 10:31 235 477 110 70 68
12 3/25/95 20:21 98 479 97 37 65
9 3/13/95 7:35 139 467 173 69 67
5 2/07/95 17:22 199 478 95 40 70
2 11/24/94 12:33 95 477 83 39 69
Total 91-240 sec. Cycl 5
CURSOR UP
CURSOR DOWN
CHOOSE
UP :
DOWN :
SELECT :