Liebert Series 600T Power Supply User Manual


 
54 Operation
Remote Monitor
The Remote Monitor Panel (optional) displays eight (8) alarms. These alarms are also available for customer use
through a set of contacts on a separate terminal board.
When the New Alarm, System Summary Alarm, or Module Summary Alarm is activated, you can get more
information at the Operator Display Panel or through a remote terminal. Refer to 3.1.14 - Communication
Interfaces.
.
The following alarms, as well as those listed above, will activate the System Summary Alarm or the Module
Summary Alarm.
SCC and Module Remote Monitor Indications
SCC Remote Monitor Indications Channel Module Remote Monitor Indications
Load On UPS CH1 Output CB Open
Load On Bypass CH2 Battery CB Open
Battery Discharging CH3 Battery Discharging
Low Battery Warning CH4 Low Battery Warning
Overload CH5 Control Failure
Ambient Over-Temp CH6 Ambient Over-Temp
System Summary Alarm CH7 Module Summary Alarm
New Alarm CH8 New Alarm
Other Alarms That Activate Summary Alarms
Other Alarms That Activate
System Summary Alarm
Other Alarms That Activate
Module Summary Alarm
Control Power Fail Blower Failed
Emergency Off Control Power Fail
Module Summary Alarm DC Capacitor Fuse Blown
Output Over/Under Frequency DC Ground Fault
Output Over-Voltage DC Over-Voltage Shutdown
Output Under-Voltage Emergency Off
Overload Transfer Equipment Over-Temperature
Static Switch Unable Inverter Fault
Low Battery Shutdown
Overload
Overload Shutdown
Rectifier Fuse Blown
Reverse Power