MGE UPS Systems Galaxy PW Power Supply User Manual


 
16
list of primary messages
LOAD PROTECTED
ON-LINE MODE
This is the normal display when there are
no alarms or problems and the load is cor-
rectly supplied by the inverter, in on-line
mode.
LOAD PROTECTED
PARALLEL ON-LINE MODE
This is the normal display when there are
no alarms or problems and the load is cor-
rectly supplied by the inverter in a parallel
UPS system, in on-line mode.
LOAD NOT PROTECTED
ON-LINE MODE
This display indicates that the load is not
supplied by the inverter, or that there is no
battery backup. The arrow
indicates
the presence of one or more problems
specified in secondary messages.
The buzzer sounds continuously.
LOAD NOT PROTECTED
PARALLEL ON-LINE MODE
Situation identical to that in the previous
screen, but for parallel UPS systems.
LOAD PROTECTED
BATTERY DISCHARGING
Remaining battery time (min) = XX
% kW used = XXX
The load is supplied by the inverter, but
the normal AC source is down or outside
tolerances and power is supplied by the
battery.
This message indicates the remaining bat-
tery time in minutes prior to inverter shut-
down and the percent load. The battery
time calculation takes into account:
the percentage of full rated load power
currently being drawn;
the type of battery;
battery temperature;
battery age.
The buzzer sounds slowly and discontinu-
ously.
LOAD PROTECTED,
LOW-BATTERY SHUTDOWN
WARNING,
Remaining battery time (min) = XX
% kW used = XXX
This message replaces the preceding if
the power outage persists and the warning
level has been reached.
The user is warned that the battery is
about to shut down.
The buzzer sounds rapidly and discontinu-
ously.
LOAD PROTECTED
ECO MODE
This is the normal display when there are
no problems: the load is supplied by the
inverter or the bypass AC source, and bat-
tery backup is available.
LOAD NOT PROTECTED
ECO MODE
This display indicates that the load is sup-
plied but has no battery backup. The
arrow
indicates the presence of one or
more problems specified in secondary
messages.
The buzzer sounds continuously.
LOAD FORCED TO INVERTER
ECO MODE
The load has been transferred to the
inverter following a specific request by the
user.
Control-panel Display
Galaxy PW
TM
100 to 225 kVA