MGE UPS Systems Galaxy PW Power Supply User Manual


 
21
inverse video:
When this function is selected, the text and
background colours are reversed (white
text on black or black text on white).
past events:
See section "logging and time-stamping".
battery test:
the screen opposite is displayed when a
battery test is requested. It indicates the
battery charge status and the remaining
service life. A manual or automatic test
may be requested,
the screen opposite is displayed during
a battery test, whether manual or automat-
ic,
the screen opposite is displayed follow-
ing a positive, manual battery test,
the screen opposite is displayed follow-
ing a negative, manual battery test,
the screen opposite is displayed follow-
ing a positive, automatic battery test. It
indicates the time since the last test and
provides access to test settings,
the screen opposite is displayed follow-
ing a negative, automatic battery test. It
indicates the time since the last test and
provides access to test settings,
the screen opposite is displayed when
the user requests access to the automatic
test settings. It is possible to modify the
interval between two automatic tests,
the screen opposite is displayed when
the battery test cannot be completed.
Control-panel Display
SELECT TIME OF NEXT TEST WITH KEYS ▼▼
CHANGE UNITS WITH
WEEK -- DAY -- HOUR --
confirm with key
TIME SINCE LAST TEST
WEEK -- DAY -- HOUR --
LAST BATTERY TEST RESULT NOT OK
NEW PARAMETERS YES = NO =
TIME SINCE LAST TEST
WEEK -- DAY -- HOUR --
LAST BATTERY TEST RESULT OK
NEW PARAMETERS YES = NO =
BATTERY TEST RESULT NOT OK
BATTERY TEST RESULT OK
TESTING BATTERY
U BATTERY = --- V
CHARGE LEVEL = -- %
REMAINING SERVICE LIFE = -- MONTH
MANUAL TEST press key
AUTO TEST press key
TEST INTERRUPTED
CHECK PRESENCE OF THE BATTERY
CHECK ALARMS
User’s Manual