CE-05171N page 31 of 44
66..33..1122 IInniittiiaall RRPPMM SSeettuupp
aa))
Assign value for Warmup RPM.
bb))
Assign value for Wait to Load RPM.
cc))
Assign value for Run Loaded RPM.
dd))
Assign value for Cooldown RPM.
66..33..1133 MMiisscceellllaanneeoouuss SSeettuupp
User can access and edit the miscellaneous settings.
aa))
Crank Attempts: Define a value for number of crank
attempts after which an over-crank sequence will be trig-
gered in the Event logic.
bb))
Controller Slave Address: Provide the value for the Modbus
Address Port. The factory default is 1.
cc))
Port 1 Mode: Select Communication Port 1 as RS232, or RS485.
dd))
Port 1 Reply Delay: To ensure sufficient time for the
Modbus reply, assign appropriate time value for Delay
Modbus Reply Port 1.
ee))
Port 1 Baud Rate: Select appropriate transmission baud rate
ff))
Port 2 Mode: Select Communication Port 2 as RS232, or RS485.
gg
))
Port 2 Reply Delay: To ensure sufficient time for the
Modbus reply, assign appropriate time value for Delay
Modbus Reply Port 2.
hh))
Port 2 Baud Rate: Select appropriate transmission baud rate
ii))
Flywheel Teeth: Define a value for Flywheel Teeth used to
calculate RPM.
The following cold temperature offset values should only be adjusted by personnel with a full working knowledge of the
Centurion in conjunction with calibrated reference equipment.
jj))
Core Cold Temp Offset: Enter a non-zero Value for Core
Temperature Adjustment (in tenths) to adjust the temperature
readings for all Thermocouple inputs on both the Main I/O Module
(C3-1). Entering a non-zero value will adjust the Cold Junction
Compensation reading used to calculate temperature.
kk))
Exp Cold Temp Offset: Enter a non-zero Value for
Expansion Board Temperature Adjustment (in tenths) to
adjust the temperature readings for all Thermocouple inputs
on Expansion I/O (C3-2). Entering a non-zero value will
adjust the Cold Junction Compensation reading used to cal-
culate temperature.
ll))
Hour Meter: The user may make hour meter adjustments.
The range is 0 – 65535 hours.
TM
C
C
C
Initial RPM Setup Screen
___________________________________
▼▼
INITIAL RPM SETUP
WARMUP RPM
00600
WAIT FOR LOAD RPM
RUN LOADED RPM
COOLDOWN RPM
▼▲ ENTER-EDIT
MORE MENUS
___________________________________
___________________________________
▼
▼
TM
C
C
C
Miscellaneous Setup Screen
___________________________________
▼▼
MISCELLANEOUS SETUP
NUMBER OF CRANK ATTEMPTS
00003
PORT 1 SLAVE ADDRESS
PORT 1 RS432/RS485
PORT 1 RESPONSE DELAY
PORT 1 BAUD RATE
▼▲ ENTER-EDIT
MORE MENUS
___________________________________
___________________________________
▼
▼