4.3.7.3 Loop Break
Loop Break: can be enabled or disabled. Loop Break is an additional safety
feature intended to monitor the rate of change of the temperature value, while
approaching the Setpoints. It is strictly intended as an additional warning system;
therefore its use is entirely optional. An active Loop Break will cause the
temperature digits to blink in a rotating pattern. If the temperature reaches the
setpoint the blinking will stop, otherwise the Break Alarm warning will flash, and
the Output will be turned off.
Loop Break Time: allows the user to determine the time interval in MM:SS
(from zero to 99 minutes and 59 seconds) that the value changes 4° Fahrenheit
or 2° Celsius.
Figure 4.16 Loop Break
Loop Break
Loop Break Time
Disabled
0
59
0-99mins
0-59secs