74
INSULATION
Power to Output
2300 Vac per 1 min. test
1500 Vac per 1 min. test (Low Voltage/Power Option)
Power to Relays/SSR Outputs
2300 Vac per 1 min. test
Relays/SSR to Relay/SSR Outputs
2300 Vac per 1 min. test
GENERAL
Line Voltage/Power:
90-240 Vac +/-10%, 50-400 Hz*; 110-375 Vdc, equivalent voltage; 5 W
* No CE compliance above 60 Hz
Low Voltage/Power Option:
12-36 Vdc or 24 Vac
**
+/-10%
, 3 W
External power source must meet Safety Agency Approvals.
** Units can be powered safely with 24 Vac power but, no Certification for CE are claimed.
External Fuse Required:
Time-Lag, IEC 127-3 recognized:
100 mA/250 V 400 mA/250 V
(Low Voltage/Power Option)
Time-Delay, UL 248-14 listed:
100 mA/250 V 400 mA/250 V
(Low Voltage/Power Option)
Environmental Conditions: 0 to 55°C (32 to 131°F), 90% RH non-condensing
Protection: NEMA-1/Type 1 front bezel
Dimensions: 48 H x 96 W x 127 mm D (1.89 x 3.78 x 5")
Panel Cutout: 45 H x 92 mm W (1.772" x 3.622 "), 1/8 DIN
Weight: 353 g (0.78 lb)