Omron CJ1W-EIP21 Network Card User Manual


 
176
Setting Tag Data Links Section 6-2
Start Connection Button:
Starts all connections for which the device is the originator.
Stop Connection Button:
Stops all connections for which the device is the originator.
Note Connections will be cut off if any of the following errors occurs in the CPU Unit
that is the originator while tag data links are active.
Fatal CPU Unit error
I/O refresh error
CPU Unit WDT error
I/O bus error
6-2-14 Clearing the Device Parameters
The device parameters saved in the EtherNet/IP Units in the EtherNet/IP net-
work can be cleared (returned to their default settings). The following proce-
dure shows how to clear the device parameters. For details on connecting to
the network from the Network Configurator, refer to 6-2-9 Connecting the Net-
work Configurator to the Network.
1,2,3... 1. Connect the Network Configurator to the network.
2. Select the icon of the EtherNet/IP Unit in which you want to clear the device
parameters. In the following example, 2 nodes are selected: 192.168.250.1
and 192.168.250.2. To select multiple nodes, press and hold the Shift Key
while selecting additional icons.