Omron CJ1W-EIP21 Network Card User Manual


 
395
FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E
IP Router Table Error
Routing Table Error
Ethernet Advanced Setting Error
BOOTP Server Error
SNTP Server Error
Address Mismatch
Non-volatile Memory Error
Total Number of Packets Received (Response)
The total number of packets received by the EtherNet/IP Unit or built-in EtherNet/IP port is returned.
Total Number of Receive Errors (Response)
The total number of packet errors detected while the EtherNet/IP Unit or built-in EtherNet/IP port was receiving
is returned.
The following types of error are detected:
Short packet errors
Alignment errors
CRC errors
Frame length errors (received frame: 1,515 bytes or more)
Communications controller overflow errors
Bit 3 Meaning
0 No error
1 Error detected (More than 8 records, or invalid IP address).
Bit 6 Meaning
0 No error
1 Error detected in routing table check.
Bit 9 Meaning
0 No error
1 An error was detected during the validity check of vendor-specific parameters for the TCP/IP Interface
Object and Ether Link Object.
Bit 10 Meaning
0 No error
1 Error detected. (A time-out occurred during communications with the BOOTP server).
Bit 10 Meaning
0 No error
1 Error detected. (The setting of the host specification (IP address or host name) of the SNTP server is not
correct, or communications with the SNTP server timed out.)
Bit 14 Meaning
0 No error
1 Error detected. (The address conversion method was set for automatic generation, but the last eight bits of
the local IP address does not match the local node address (FINS node address), or the host section other
than the last byte of the local IP address is non-zero.)
Bit 15 Meaning
0 No error
1 Error detected. (The non-volatile memory’s service life has expired, or the memory has failed).