Omron CJ2M-CPU3@ Network Card User Manual


 
105
IP Addresses in FINS Communications Section 5-2
Models that Can Use the
Combined Method
5-2-5 Pairing IP Addresses and FINS Node Addresses
The following table shows the methods for pairing IP address and FINS node
addresses, and the relation between fixed and variable address, for both
FINS/UDP and FINS/TCP.
Product Model/Series/
Version
Supports combined
method?
CS-series Ethernet
Unit
100BASE-TX CS1W-ETN21 Yes
10BASE-5 CS1W-ETN01 No
10BASE-T CS1W-ETN11 No
CJ-series Ethernet
Unit
100BASE-TX CJ1W-ETN21 Yes
10BASE-T CJ1W-ETN11 No
CV/CVM1-series
Ethernet Unit
10BASE-5 CV500-ETN01 No
FinsGateway Version 4.xx or
lower
No
Version 2003 or
higher
Ye s
Programmable Terminal NS Series No: Set manually. FINS
communications are not
possible with personal
computers set automati-
cally by DHCP.
Open Network Controller (ONC) ---
Communi-
cations
method
Method of pairing
of IP addresses
and FINS node
addresses
IP address determination Client (personal
computer of PLC)
Server (PLC)
FINS node
address
IP address FINS node
address
IP address
FINS/UDP By pairing FINS
node addresses with
IP addresses in
Ethernet
IP address
conversion
Automatic gen-
eration method
(static)
Fixed Fixed Fixed Fixed
Automatic gen-
eration method
(dynamic)
Fixed Fixed or
variable
Fixed Fixed
IP address table
method
Fixed Fixed or
variable
Fixed Fixed
Combined
method
Fixed Fixed or
variable
Fixed Fixed
FINS/TCP By automatic conver-
sion of FINS node
addresses at Ether-
Net/IP Unit and
remote node (and
then sending and
receiving data)
Automatic Connection
method (auto-
matic FINS
node address
conversion)
Fixed or
can be allo-
cated auto-
matically
when not
determined.
Fixed or
variable
Fixed Fixed