SSI America EPS2U Power Supply User Manual


 
SSI
EPS2U Power Supply Design Guide, V2.1
Table 4: AC Line Sag Transient Performance
AC Line Sag
Duration Sag Operating AC Voltage Line Frequency Performance Criteria
Continuous 10% Nominal AC Voltage ranges 50/60 Hz No loss of function or performance
0 to 1 AC
cycle
100% Nominal AC Voltage ranges 50/60 Hz No loss of function or performance
>1 AC cycle >10% Nominal AC Voltage ranges 50/60 Hz Loss of function acceptable, self
recoverable
Table 5: AC Line Surge Transient Performance
AC Line Surge
Duration Surge Operating AC Voltage Line Frequency Performance Criteria
Continuous 10% Nominal AC Voltages 50/60 Hz No loss of function or performance
0 to ½ AC
cycle
30% Mid-point of nominal AC
Voltages
50/60 Hz No loss of function or performance
5.8 AC Line Fast Transient Specification
STATUS
Recommended
The power supply shall meet the EN61000-4-5 directive and any additional requirements in IEC1000-4-5:1995
and the Level 3 requirements for surge-withstand capability, with the following conditions and exceptions:
These input transients must not cause any out-of-regulation conditions, such as overshoot and
undershoot, nor must it cause any nuisance trips of any of the power supply protection circuits.
The surge-withstand test must not produce damage to the power supply.
The supply must meet surge-withstand test conditions under maximum and minimum DC-output load
conditions.
- 11 -