8.3.2.2 MultiRecord Area
Implement as defined by the IPMI FRU document. The following record types shall be used on this power supply:
• Power Supply Information (Record Type 0x00)
• DC Output (Record Type 0x01)
• No other record types are required for the power supply.
MultiRecord information shall be defined as follows:
Table 32: FRU Device Product Information Area
Field Name (PS Info) Field Information Definition
Overall Capacity (watts) 480
Peak VA 550
Inrush current (A) 50
Inrush interval (ms) 5
Low end input voltage range 1 90
High end input voltage range 1 140
Low end input voltage range 2 180
High end input voltage range 2 264
A/C dropout tol. (ms) 20
Binary flags Set for: Hot Swap support, Autoswitch, and PFC
Peak Wattage
Set for: 10 s, 550 W
Combined wattage Set for 5 V & 3.3V combined wattage of 115 W
Predictive fail tach support Not supported, 00h value
Field Name (Output) Field Description:
Five outputs are to be defined from #1 to #5, as follows: +3.3 V, +5
V, +12 V, -12V, and +5 VSB.
Output Information Set for: Standby on +5 VSB, No Standby on all others.
All other output fields Format per IPMI specification, using parameters in the EPS12V
specification.