Toshiba 431A Network Hardware User Manual


 
10
4300 Series Ancillary Cabinets Installation and Operation Manual
CAUTION
Install the ancillary cabinet in a controlled environment.
Improper storage and installation environment may deteriorate
insulation, shorten component life and cause malfunctions.
See Table 5.1 - UPS Installation Environment Standards
DO NOT tilt the ancillary cabinet more than 10° from upright
position.
Tilting the ancillary cabinet more than 10° may cause crushing,
trapping or other personal injuries and cause physical damage to
internal components.
WARNING
Keep the SPECIFIED CLEARANCE around the UPS.
Inadequate space around the UPS makes it difcult to perform
maintenance/inspections, will lead to insufcient ventilation, and/or
cause malfunctions.
Install anchor bolts to secure the UPS to the installation oor.
The UPS may fall during an earthquake if the anchor bolts are not
installed and secured.
Only factory authorized personnel should relocate, modify, or
replace parts in the ancillary cabinet after initial installation.
Electrical shock, injury or ancillary cabinet failure may occur if non-
authorized technicians attempt to modify or relocate the UPS.
Please contact Toshiba Customer Support Center if you plan to move
ormakemodicationstotheUPS
5 Installation Precautions