EtherNet/IP parameters
Title
Communi
cation No.
Function Description
Factory
setting
c536 C536 EtherNet Error
Monitor of the EtherNet error.
0: No error/clear error
1: Modbus TCP IO Scanning timeout
2: Network overload
3: Loss of Ethernet carrier
-
c554 C554 Web service (*3)
Enables web server.
0: Disable
1: Enable
1
c555 C555 Drive Status
Monitor the inverter status.
3: Gate Block
4: Run
23: Fault
-
Modbus TCP parameters
Title
Communi
cation No.
Function Description
Factory
setting
c600-
c603
C600-
C603
IP Master (*3) The IP address for PLC(Master) of the Modbus TCP.
0.0.0.0
c604 C604 IO Scan active (*3)
Enables IO Scan function.
0: Non-active
1: Active
0
(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.
Warning
Mandatory
action
Set up “Communication error trip function (c100 to c103 and c523)” to stop the
inverter when EtherNet/IP™ - Modbus® TCP communication is deactivated.
When the parameters are changed, please reset (power supply reset or f899=1) the
inverter for the changes to take effect.