Toshiba IPE002Z Switch User Manual


 
E6581741
- 35 -
4.9. Parameter Objects (0x65)
Class code 0x65. This object provides VF-MB1/S15’s Parameter access.
Range Address accessed:
Input Instance Real Logical address in Drive accessed
0x0001-0xFFFF 0x0001-0xFFFF
* Refer to "Class Attributes" when the instance is 0.
* If you want to access the au1, please use the "Application Objects (64 hex)."
Class Attributes
Instance Attribute ID Access Name Data type Details Value
1 Get Revision UINT Revision of this object
1
2 Get Max Instances UINT Maximum instance number of an
object currently created in this class
level of the device.
65535
3 Get Number of Instances UINT Number of object instances currently
created at this class level of the
device.
65535
6 Get Max ID of class
attributes
UINT The attribute ID number of the last
class attribute of the class definition
implemented in the device.
7
0
7 Get Max ID of instance
attribute
UINT The attribute ID number of the last
instance attribute of the class
definition implemented in the device.
3
Class Services
Service Code Service Name Description of Service
0x0E Get_Attribute_Single Read one attribute
Instance 1 Attribute
Instance Attribute ID Access Name Data type Details
See
below
3 Get/Set parameter UINT
Parameter corresponding to the Instance
address
Instance Services
Service Code Service Name Description of Service
0x0E Get_Attribute_Single Read one attribute
0x10 Set_Attribute_Single Write one attribute
Attribute ID of all parameters are 3. Moreover, about the instance ID of each parameter, it
becomes "parameter communication number".
About the details of the contents of a parameter please refer to VF-MB1 instruction
manual or VF-S15 instruction manual.
Example 1:
When "ACC. time" is set to 5 s, since the minimum unit is 0.1s,
5 / 0.1 = 50 = 32H
Since the communication umber of "Acc. time" is "0009", it writes "32H" is instance ID "0009."