Toshiba IPE002Z Switch User Manual


 
E6581741
- 20 -
3.2.4.13. fc91 (Alarm code)
bit
Function 0 1
Remarks
(Code displayed on
the panel)
0 Over-current alarm Normal Alarming c flicking
1 Inverter over load alarm Normal Alarming l flicking
2 Motor over load alarm Normal Alarming l flicking
3 Over heat alarm Normal Alarming h flicking
4 Over voltage alarm Normal Alarming p flicking
5 Main circuit undervoltage alarm Normal Alarming -
6 main device overheat alarm Normal Alarming l flicking
7 Under current alarm Normal Alarming -
8 Over-torque alarm Normal Alarming -
9 Braking resistor overload alarm Normal Alarming -
10 Cumulative operation hours alarm Normal Alarming -
11 Option communication alarm Normal Alarming -
12 Serial communication alarm Normal Alarming -
13 MOFFMS (MSrelay off or MOFF) Normal Alarming -
14 Stop after instantaneous power off -
Dec., Under
stop
Refer to f302
value
15 Stop after LL continuance time -
Dec., Under
stop
Refer to f256
value
3.2.4.14. fd06 (Input TB Status)
bit TB Name Function (Parameter) 0 1
0 F Input terminal function selection 1 (f111)
1 R Input terminal function selection 2 (f112)
2 RES Input terminal function selection 3 (f113)
3 S1 Input terminal function selection 4 (f114)
4 S2 Input terminal function selection 5 (f115)
5 S3 Input terminal function selection 6 (f116)
6 VIB*1 Input terminal function selection 7 (f117)
7 VIA*1 Input terminal function selection 8 (f118)
OFF ON
5 to 15 (Reserved) - Undefined
Note: Don't use the reserved bit for the judgment.
*1: VIA/ VIB are input terminal function when f109 is logic input.
*The input terminal function is selected by each parameter.
Example: Data set for FE06 when the F and RES terminals are ON = 0005H
BIT15 BIT0
0 0 0 0 000000000101
FE06:
0
0
0
5