Toshiba MBP-100 Network Card User Manual


 
43
Table 2: Global Data Assignment Example (x=Don’t Care)
Point #
Get
Node
Get Offset Put Offset Note
1 3 2 DISABLED Get from node #3
2 x DISABLED DISABLED No global data access
3 8 5 DISABLED Get from node #8
4 8 5 DISABLED Get from node #8
5 3 3 DISABLED Get from node #3
6 x DISABLED 0 Put
7 x DISABLED 1 Put
8 x DISABLED 4 Put
9 x DISABLED DISABLED No global data access
10 x DISABLED 5 Put
11 x DISABLED 7 Put
12 x DISABLED 8 Put
With the indicated global data assignments, we can get a logical overview of
the three relevant global data areas from Figure 22, Figure 23 and Figure 24.
ignored ignored
Point #1
value
Point #5
value
Offset
0
Offset 1 Offset
2
………
Offset
3
………
ignored
Offset 31
Figure 22: "Get" Global Data From Node Address #3
ignored
………
Point #3 and
#4 value
ignored
Offset
0
………
Offset 5
………
Offset
6
………
ignored
Offset 31
Figure 23: "Get" Global Data From Node Address #8
unused
Point #11
value
Point #12
value
unused
Offset 6
Offset 7 Offset 8
………
Offset 9
………
unused
Offset 31
Point #6
value
Point #7
value
unused unused
Offset 0
Offset 1 Offset 2 Offset 3
Point #10
value
Offset 5
Point #8
value
Offset 4
Figure 24: "Put" Global Data From MBP-100