Toshiba MBP-100 Network Card User Manual


 
59
Signal
Ground
(TB:3)
B
(TB:2)
A
(TB:1)
Figure 36: 700-Series ASD Connections
Note that although the 700-series ASD also supports the Modbus RTU
protocol, the initial ASD firmware did not support the Modbus RTU protocol
in 2-wire format. Therefore, using the Mitsubishi protocol may be the only
available method to communicate with the gateway (ASD parameter 549
must be “0”). Contact Mitsubishi Technical Support for more information.
The slave response timeout is determined via the gateway’s RS485 port
timeout value setting. If the timeout value is set to 0, a default timeout time
of 2s is used.
ASD communication characteristics are dictated by parameters 117-124
(PU port) and 331-341 (RS485 port). Most of these parameters can be set
as desired by the user. However, the following parameters must be set as
indicated to successfully connect to the gateway:
Parameter 119/333 (stop bits/data bits).........Must be set for 8 data bits
Parameter 123/337 (wait time setting)...........Must be set to 9999
Parameter 124/341 (CR/LF selection)........... Must be set to 1 (CR only)
ASD parameter number entry radix is decimal (e.g. 10 = 10
10
)
Any numerically-addressed parameter defined by the Mitsubishi protocol
reference manual is directly accessible (base frequency = parameter #3,
etc.). However, some ASD data objects do not have parameter numbers
assigned by Mitsubishi. For these data objects, the additional parameter
numbers indicated in Table 6 have been assigned. For further information