6.3 Panel Controls
When the unit has stopped due to failure, be sure to remove the
memory card before resetting the LCD Failure Error screen on the
panel, so you can give it to the service person.
Resetting (restarting) the UPS without removing the memory card will
delete the data needed to determine the cause of the failure.
Every effort has been made to ensure safety in unit handling.
However, when removing the memory card, do not touch the other
sections of the unit.
NOTES
Touching the other sections of the unit may result in electric shock.
The locations of the controls on the panel are shown in Figure 6.3.1. For the functions of
each of the controls, see Section 6.3.1 "Panel Key-switch" and Section 6.3.2 "Panel Keys."
NOTE ***
Figure 6.3.1 Panel Controls
(For individual battery systems. For HS or AHH batteries.)
Do not use the keypad on
graphic display panel l.
This keypad is used to
change the internal
settings and should
only be used by
maintenance
personnel.
It is not used during
normal operation.
* This will be the "FLOAT" key for MSE individual battery systems.
** This will be the "PROTECTION" LED for MSE individual battery
systems.