- 38 -
6 F 3 H 1 0 0 1
(2) Table 8.5 shows the procedure used to change manually from equalized charge to
floating charge.
After the charging mode has been changed to equalized charge using the procedure
on the previous page, the mode will automatically change back to floating charge after
a set period of time has elapsed. Therefore, normally there is no need to change the
mode manually as described below.
Table 8.6 Changing From Equalized Charge to Floating Charge
Step Procedure LCD/LED Status (After Execution)
1 Check to make sure
that the "EQUAL
CHARGE" LED is lit.
2 Hold down the "FLOAT
/ EQUAL" key (h in
Figure 6.3.1 on page
14) for at least 0.5
second.
→ Change to floating
charge is complete.
The "FLOAT CHARGE" LED lit.
The "EQUAL CHARGE" LED unlit.
UPS SUPPLY
UPS SUPPLY
AC-VO 200[V]
AC-
I O 50[%]
AC-VO 200[V]
AC-
I O 50[%]
BATTERIES
AC
SWITCH
UPS
BYPASS
DISCHARGE
FLOAT CHARGE
EQUAL CHARGE
~
AC INPUT
~
CONVERTER
~
INVERTER
~
AC OUTPUT
BYPASS INPUT
~
BATTERIES
AC
SWITCH
UPS
BYPASS
DISCHARGE
FLOAT CHARGE
EQUAL CHARGE
~
AC INPUT
~
CONVERTER
~
INVERTER
~
AC OUTPUT
BYPASS INPUT
~