8.3 Procedures
8.3.1 Startup
Table 8.1 shows the procedure used to start up the UPS.
LED status : Unlit : Lit : Blinking
Table 8.1 Startup Procedures
Step Procedure LCD/LED Status (After Execution)
1 Turn on the control
power supply switch
(8A) on the panel.
2 Turn on the bypass AC
input 52C and the AC
output 52L circuit
breakers.
(The UPS will change
to bypass power
supply status and AC
output voltage will be
generated.)
3
Turn on the precharge
circuit switch (6CH)*.
* The control power supply switch 8A is left in the on state (Do not turn this switch off.)