Table 8.9 Changing From Maintenance Bypass to UPS Power Supply
Step Procedure LCD/LED Status (After Execution)
1 Same as steps 1-4 in
Section 8.3.1 “Startup”
2
Turn OFF maintenance
bypass AC circuit breaker
52M. *
,
**
,
***
3 Same as steps 5-11 in Section 8.3.1 “Startup”
→Change to UPS power supply complete.
* During load operation, ALWAYS operate the circuit breakers in the following order:
52C ON → 52L ON → 52M OFF
** UPS power supply is disabled when the 52M circuit breaker is in the on state.
*** This operation is different from that displayed in the help message on the screen.
Be sure to perform the operation as described here.