- 33 -
6 F 3 H 1 0 0 1
8.3.3 Stop
Table 8.3 shows the procedure used to stop the UPS.
Table 8.3 Stop
Step Procedure LCD/LED Status (After Execution)
1 Change to bypass
supply as described in
Table 8.2 on page 31.
2 Hold down the "STOP"
key (e in Figure 6.3.1
on page 14) for at least
0.5 second.
The “FLOAT CHARGE” and “CONVERTER”
and “INVERTER” LEDs unlit.
BYPASS
BYPASS
AC-VO 200[V]
AC-
I O 50[%]
PRESS ‘UPS’ SWITCH
RESTART : PRESS ‘RUN’ SWITCH
SHUTDOWN : MOVE #72B TO ‘OFF’
AC
SWITCH
UPS
BYPASS
BATTERIES
DISCHARGE
FLOAT CHARGE
EQUAL CHARGE
~
AC INPUT
~
CONVERTER
~
INVERTER
~
AC OUTPUT
BYPASS INPUT
~
BATTERIES
AC
SWITCH
UPS
BYPASS
DISCHARGE
FLOAT CHARGE
EQUAL CHARGE
~
AC INPUT
~
CONVERTER
~
INVERTER
~
AC OUTPUT
BYPASS INPUT
~
The “UPS” LED unlit and “BYPASS” LED lit.