Xantrex Technology XDI2048 Power Supply User Manual


 
Remote Communication & Monitoring
4-6 TM-DIOP-01XN-01
You can use Table 4-2 to record your own settings.
Resetting
To reset the Ethernet settings the cover will have to be removed to put a
jumper onto the control card. When the Ethernet is reset, its settings will
be changed to the default values as shown in Table 4-3.
To reset the Ethernet:
1. Remove the XDI unit from it’s rack mount.
2. Remove the top cover (Figure 4-3, “Removing Unit’s Top Cover” on
page 4–7).
3. Place a jumper on SW2 (Figure 4-4, “Ethernet Reset Jumper” on page
4–8).
4. Replace top cover.
5. Apply power to the XDI by putting it back into the rack mount and
turning the unit on.
6. Wait 10 seconds.
7. Remove the XDI from the rack mount.
8. Remove the top cover.
9. Remove the jumper on SW2.
10. Replace the top cover.
Table 4-2
User Configured Settings
Setting Value
Default IP
Gateway IP
Sub-Net Mask
Domain Name Server 1
Domain Name Server 2
SMTP (email) Server
Email Alert Address
Password