Xantrex Technology XDI2048 Power Supply User Manual


 
Specifications
A-2 TM-DIOP-01XN-01
Inverter Specifications
Electrical Specifications
Input Voltage, Current, Power, Frequency Ranges
Output Voltage, Current, Power, Frequency Ranges
Nominal Input - 48 VDC
Input Range - 40 to - 60 V (meets all specification)
Safe Input Range ± 80 Vdc (will not damage unit)
Maximum Input Current 90 A (at 40 V in, max 3 kW surge output,
5s max)
Nominal input Current 36 A (at 48 V input, 1500 W output)
Maximum Input Current Ripple < 1% Input Current
DC Side Voice Band Noise Limit less than 32 dBrnc (C-message
weighting)
Over Current Protection electronic limit on input boost converter
stage, 60 A fuse on DC input Inverter
stage output fuse for extreme faults
Inrush Current Controlled 40 A typical at 48 V < (2x I
rated
)
Waveform True Sinusoidal
THD < 3% Typical for linear loads
Output Voltage 120 Vac/60 Hz
230Vac/50Hz
Voltage Regulation < -10%/+4% over full operating range
Frequency Stability ± 0.05%
Frequency Accuracy 60/50 Hz ± 0.1%
Fully Isolated input to output
Power Rating 2 kVA/1.5 kW Max, over full operating
temperature range
Peak Output Current Into
Nonlinear Load
50A
pk
maximum for 120VAC
25A
pk
maximum for 230VAC