Xantrex Technology XDI2048 Power Supply User Manual


 
Operating Instructions
TM-DIOP-01XN-01 4-19
Automatic Shutdown Email
When the inverter shuts down due to a fault or a user shutdown, the
Ethernet interface will attempt to send an email to the configured “Email
Alert Address” using the configured “SMTP Server” (see “Network
Connection” on page 4–9).
Contents of the email:
From: XDI <serial number>
To: <Email Alert Address>
Subject: Unit has shutdown
Body:
Serial # <Serial> at <IP> has shutdown. <Shutdown_Code>
The shutdown code list is a list of decimal values that represent specific
shutdown conditions (Table 4-7, “Shutdown Code” on page 4–19)
currently exhibited by the inverter. Each shutdown code is separated by a
space.
Important:
By the time you have received the email, if the inverter has
shutdown due to a fault, the inverter may have already corrected the problem.
Table 4-7
Shutdown Code
Code Fault Description
16 Reserved
15 Reserved
14 Reserved
13 Input stage voltage out of range
12 DC link stage over voltage
11 Output stage over voltage
10 Multiple output stage over current
9 Output overload
8 Synchronization error
7 Over temperature
6 Output disabled via interlock
5 Output disabled via interface command
4 Output disabled by user.
(To enable, toggle interlock or interface command)
3 DC link stage under voltage
2 Output stage under voltage
1 Output stage over current