ADC ETU-751C Network Card User Manual


 
700-701-100-02 Functional Description
UTU-701 and ETU-751 List 1 August 9, 2002 13
Power Sources
The line and desktop units receive power from the following sources:
A shelf-mounted UTU-701C receives power from a local source of -36 Vdc to -72 Vdc.
An enclosure mounted UTU-701C receives power from a local source of -36 Vdc to -72 Vdc or from the
enclosure’s built-in AC-to-DC power supply (when provided).
The ETU-751C desktop unit receives power from a source of 100 to 240 volt, 50 or 60 Hz, AC power.
Input voltage for the UTU-701C line unit (nominal -48 Vdc, tolerance -36 to -72 Vdc) must be
supplied by an isolated DC source that complies with TNV or earthed SELV requirements of the
latest version of IEC 950.
The single-pair rate selectable HDSL units (local and remote) must be locally powered.