Emergency Manual Operation
InfraStruXure Power Generation System 23
How to power the load from the generator
1. Set the ATS Automatic Operation switch to Disable.
2. Ensure the Source 2 switch is OFF (
).
3. At the generator:
a. Set the
/Manual/Auto switch on the generator
control panel to Manual.
b. Press the Manual Run/Stop button if you need to start
the generator.
Pressing this button activates the engine control system
and the starting system. The starter will begin cranking
and, after a few seconds, the engine should start.
4. Turn the Source 1 switch OFF (
):
a. Set the selector on the Source 1 switch to Manual.
The operating lever will swing out when the selector is
set to Manual.
b. Turn the Source 1 switch counterclockwise to OFF
(
). Use the operating lever key for easier operation.
Press