American Power Conversion 250 A Power Supply User Manual


 
How to Add Sub-Feed Output Distribution Circuit Breakers to the ATS
InfraStruXure Power Generation System 71
Combination #6.
Combination #7.
Combination #8.
Combination #9.
Combination #10.
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm)
T1 3-pole 1 2 3.00 in (76.2 mm) 7.2 in (183.2 mm)
T1 1-pole 6 12 6.00 in (152.4 mm) 1.2 in (30.8 mm)
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm)
T1 3-pole 1 2 3.00 in (76.2 mm) 7.2 in (183.2 mm)
T1 1-pole 7 14 7.00 in (177.8 mm) 0.2 in (5.4 mm)
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm)
T1 3-pole 0 0 0 10.2 in (259.4 mm)
T1 1-pole 8 16 8.00 in (203.2 mm) 2.2 in (26.2 mm)
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm)
T1 3-pole 0 0 0 10.2 in (259.4 mm)
T1 1-pole 9 18 9.00 in (228.6 mm) 1.2 in (30.8 mm)
Type of Breaker # of Modules # of Breakers Space Occupied Space Remaining
T3 3-pole 0 0 0 10.2 in (259.4 mm)
T1 3-pole 0 0 0 10.2 in (259.4 mm)
T1 1-pole 10 20 10.00 in (254.0 mm) 0.2 in (5.4 mm)