American Power Conversion MX28B200 Power Supply User Manual


 
Page 30 MX28B200/400 48 VDC User’s Manual (990-9133)
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Circuit Breaker 1 Alias
Security Level {1}
[MODULES/CIRBKR/ALIAS]
Circuit Breaker 24 Alias
Security Level {1}
[MODULES/CIRBKR/ALIAS]
An alternate name (alias) that can be
assigned to a circuit breaker if desired.
An alternate name (alias) that can be
assigned to a circuit breaker if desired.
Cir Bkr 1 m+
-48V
Cir Bkr 24 m+
-48V
Circuit Breaker 1 Tripped
Security Level {1}
[MODULES/CIRBKR/SET-
ALM]
Circuit Breaker 24 Tripped
Security Level {1}
[MODULES/CIRBKR/SET-
ALM]
An alarm that indicates Circuit Breaker 1
is tripped.
An alarm that indicates Circuit Breaker
24 is tripped.
Cir Bkr 1 Alm m+
Major
Cir Bkr 24 Almm+
Major
Compensation High Knee
Security Level {1}
[BATT/COMP]
The temperature compensation high
knee is the point above which there is no
additional battery voltage compensation
for further increases in temperature.
Comp Hknee m+
40.0 C
Compensation Low Knee
Security Level {1}
[BATT/COMP]
The temperature compensation low knee
is the point below which there is no
additional battery voltage compensation
for further decreases in temperature.
Comp Lknee m+
0.0 C
Compensation Method
Security Level {1}
[BATT/COMP]
One of three parameters that control the
DC output voltage. Activate “ON” or de-
activate “OFF” battery temperature
compensation.
Comp Method m+
OFF
Compensation Temperature
Coefficient
Security Level {1}
[BATT/COMP]
Temperature compensation coefficient
between low knee and high knee in
mV/cell/°C. (Compensation equals zero
at 25°C.)
Comp TC m+
- 3.00mV
Control Unit Revision
{Status Only}
[SYSTEM/SETUP]
Hardware revision level of the control
unit. This parameter cannot be changed.
Cntrl Rev +
000002
Date
Security Level {1}
[SYSTEM/DATE]
Internal system calendar date. Used as
a date stamp in the event log.
Date m+
DEC 16 1999
Display Type
{Status Only}
[SYSTEM/SETUP]
Type number for the control unit display.
This parameter cannot be changed.
Display Type +
000255
Fahrenheit Scale
Security Level {1}
[SYSTEM/SETUP]
Enables selection of Fahrenheit or
Celsius temperature scale (Fahrenheit
OFF” displays readings in °C).
Fahrenheit m+
OFF