American Power Conversion MX28B200 Power Supply User Manual


 
MX28B200/400 48 VDC User’s Manual (990-9133) Page 35
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Rectifier Fan Fail Alarm Status
{Status Only}
[MODULES/RECT/INFO]
The status will be “ON” if the rectifier fan
has failed. NOTE: This information
can be viewed for each rectifier
installed by using the horizontal arrow
keys.
Rect 1 FF #
OFF
Rectifier Fault Alarm (RFA)
Status
{Status Only}
[MODULES/RECT/INFO]
The status will be on if the rectifier output
has failed. NOTE: This information
can be viewed for each rectifier
installed by using the horizontal arrow
keys.
Rect 1 RFA #
OFF
Rectifier RFA Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]
The output relay that is energized or
special rectifier alarm group n of N that
occurs when a rectifier output has failed.
Rect RFA Alm m+
n of N
Rectifier Standby Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]
The output relay that is energized or
special rectifier alarm group n of N that
occurs when the control unit is holding a
rectifier in the standby mode.
Rect Stdby Almm+
n of N
Rectifier Standby Alarm Status
{Status Only}
[MODULES/RECT/INFO]
The status will be “ON” if the control unit
is holding the rectifier in the standby
mode. NOTE: This information can be
viewed for each rectifier installed by
using the horizontal arrow keys.
Rect 1 Stdby #
OFF
Store Configuration
Security Level {1}
[SYSTEM/DIAG]
Setting this parameter to “Enable” will
cause the current rectifier configuration
to be stored (the display toggles back to
“Disable” after entry).
Store Cfg m+
Disable
System Current
{Status Only}
[STATUS]
The total system output current
(calculated as the sum of the individual
rectifier output currents).
Sys Current +
145.8 A
System High Temperature
Alarm
Security Level {1}
[SYSTEM/SET-ALM]
The output relay energized if the System
Temperature exceeds the system high
temperature threshold.
Sys HT Alm m+
Minor
System High Temperature
Threshold
Security Level {1}
[SYSTEM/SET-ALM]
System Temperature is ambient
temperature measured inside the
controller. An alarm will be reported if
temperature is higher than the
temperature entered.
Sys HT Thr m+
70.0 C
System High Voltage alarm
Security Level {1}
[SYSTEM/SET-ALM]
The output relay energized if the System
Voltage is above the System High
Voltage threshold.
Sys HV Alm m+
Minor
System High Voltage
Threshold
Security Level {1}
[SYSTEM/SET-ALM]
System Voltage is bus voltage measured
by the controller. An alarm will be
reported if voltage is higher than the
voltage entered.
Sys HV Thr m+
-58.00 V
System Low Temperature
Alarm
Security Level {1}
[SYSTEM/SET-ALM]
The output relay energized if the System
Temperature is below the System Low
Temperature threshold.
Sys LT Alm m+
Minor