American Power Conversion MX28B200 Power Supply User Manual


 
Page 32 MX28B200/400 48 VDC User’s Manual (990-9133)
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Input Relay 1
Security Level {1}
[SYSTEM/IN-RLY/RLY-MAP]
Input Relay 4
Security Level {1}
[SYSTEM/IN-RLY/RLY-MAP]
The Output Relay that is energized when
an external contact closure or opening at
the Input Relay 1 connection changes
state.
The Output Relay that is energized when
an external contact closure or opening at
the Input Relay 4 connection changes
state.
In-Rly 1 Alm m+
Ignore
In-Rly 4 Alm m+
Ignore
Input Relay 1 Alias
Security Level {1}
[SYSTEM/IN-RLY/ALIAS]
Input Relay 4 Alias
Security Level {1}
[SYSTEM/IN-RLY/ALIAS]
An alternate name (alias) can be
assigned to Input Relay 1 if desired.
An alternate name (alias) can be
assigned to Input Relay 1 if desired
In-Rly 1 m+
Input Relay 1
In-Rly 4 m+
Input Relay 4
Lamp Test
Security Level {1}
[SYSTEM/DIAG]
Setting Lamp Test to “ON” will turn on
the “MAJOR”, “MINOR”, “NORMAL”,
“MAJ”, and “MIN” LEDs on the control
unit front panel.
Lamp Test m+
OFF
LVD 1 or 2 Option
Security Level {1}
[MODULES/LVD/SET-ALM]
Must be set to “Enable” if the unit has an
LVD. If the unit has an LVD, but it is
disabled, the controller will not
disconnect the LVD.
LVD Option m+
Enable
LVD 1 or 2 Reset
Security Level {1}
[MODULES/LVD/PARAM]
LVD Reset (reconnect) threshold voltage.
LVD Reset m+
-48.00 V
LVD 1 or 2 Trip
Security Level {1}
[MODULES/LVD/PARAM]
LVD Trip (disconnect) threshold voltage.
LVD Trip m+
-42.00 V
LVD Alarm
Security Level {1}
[MODULES/LVD/SET-ALM]
The output relay that is energized when
the controller opens the LVD. If unit has
a battery LVD, no power will be available
to turn on any Output Relays.
LVD Open Alm m+
Minor
Model Programming
Security Level {2}
[SYSTEM/SETUP]
Model type number for the MX28B DC
power plant
NOTE: Changing the model number
causes the system to reinitialize.
Model m+
MX28B-200/400
OEM R Gain
Security Level {2}
[OEM]
Voltage gain adjustment for factory
calibration of system voltage
readings/settings.
OEM R Gain m+
1.000 V
OEM R Offset
Security Level {2}
[OEM]
Voltage offset adjustment for factory
calibration of system voltage
readings/settings.
OEM R Offset m+
0.000 V
OEM S Gain
Security Level {2}
[OEM]
Current gain adjustment for factory
calibration of battery current
readings/settings.
OEM S Gain m+
1.000 A