American Power Conversion PD60H5HK1 Power Supply User Manual


 
PDU Display Interface
18 60kW InfraStruXure PDU—Operation and Configuration
Panel Configuration
Configure the branch metering settings for each circuit breaker on
the distribution panel, or configure both panels simultaneously.
To configure a circuit breaker, select the range that includes the
circuit breaker. The top line of selections on the screen apply to
the top distribution circuit breaker panel on the PDU. The bottom line of selections apply to the
bottom distribution circuit breaker panel on the PDU. The panel position numbers on the screen
correspond to the numbers on the distribution panel. (Odd numbers are on the left; even numbers are
on the right.) Once you have selected the correct range, configure the settings for each circuit breaker
in the range:
Pos: The panel positions in the selected range.
Breaker: Two configurable items:
The circuit breaker rating, in amps.
The circuit breaker tie indicator: Define the number of associated panel positions. You can
associate positions with circuit breakers, which enables you to view status about each circuit
breaker and receive alarm notification when any of a circuit breaker’s poles are above or below
the configured branch circuit limit. You can also associate together panel positions that are
logically tied together. For example, you can associate together panel positions for three
separate circuit breakers that are connected to the same PDU power cord and that feed power to
the same equipment enclosure.
To configure the values on this screen:
1. From the first column, use the arrow keys to scroll up or down to the pole position you want to
configure.
2. Press the
ENTER key to move to the item you want to configure in the third column (the circuit
breaker rating or the circuit breaker tie indicator).
3. Scroll again to select the value you want for the circuit breaker rating or the circuit breaker tie
indicator. To associate one panel position with the next position in the list, choose the +
character as the tie indicator immediately following the circuit breaker rating. To indicate that
the position is not associated with the next panel position in the list, choose the
] character as
the tie indicator immediately following the circuit breaker rating. When you change the
+ or ]
character that follows the circuit breaker rating in one row, the
+ or [ character before the
circuit breaker rating in the next row also changes to indicate the changed association between
the panel positions.
For example, this screen shows three, single-pole, 16A,
associated circuit breakers occupying positions 08, 10, and
12 on the top right distribution panel.
Panel Configuration
Select Range:
[01..41] [02..42]
Pos
08
10
12
Breaker
[ 16A +
+ 16A +
+ 16A ]