American Power Conversion PD60H5HK1 Power Supply User Manual


 
60kW InfraStruXure PDU—Operation and Configuration 55
Specifications
InfraStruXure PDU
Electrical With Transformer Without Transformer
Output
Voltage AC L1, L2, L3, N, PE 400/230V: 3W, N, PE
Full Load Rating 60kVA 100A
Nominal Current 167A 180A
Number of Distribution Panels 2 × 225A, 42-position
Max. Distribution Breaker Size 150AT 150AT
Main Breaker 175A MCCB, 100% rated 225A MCCB
Input
Nominal Voltage 400V 400/230V
Frequency 57–63Hz 47–70Hz
Voltage AC L1, L2, L3, PE 400/230V: 3W, N, PE (WYE)
Nominal Current 167A 100A
Disconnect 225A molded case switch N/A
Physical
Dimensions (H×W ×D)
PDU
2159 × 610 × 864 mm
(85 × 24 × 34in)
2159 × 610 × 864 mm
(85 × 24 × 34in)
Weight
PDU only 410kg (904lb) 204kg (450lb)
PDU with 28 cables 556kg (1226lb) 351kg (774lb)
Relay Outputs
Nominal switching capacity 1A at 30VDC
Maximum switching power 30W
Maximum switching voltage 60VDC
Maximum switching current 2ADC
Maximum carrying current 2ADC
Surge Ratings 2kV per Bellcore TA-NWT-001089
1.5kV per FCC part 68