APC 10-40 KVA 380/400/415 V Power Supply User Manual


 
Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation8
Anchor the UPS and additional XR Battery or UPS
Enclosure(s) (optional)
Note: Enclosures can be kept apart or assembled and anchored with interconnection plates and
brackets: SUVTOPT004: 352 mm (13.85 in) UPS enclosure to XR enclosure, SUVTOPT005:
523 mm (20.59 in) UPS enclosure to XR enclosure, or SUVTOPT006: XR enclosure to XR
enclosure.
Note: A baying kit includes three U-shaped floor anchoring brackets. In situations where a
UPS or XR Battery Enclosure must be added to an existing configuration of two or more bayed
together enclosures, only one of the U-shaped floor anchoring brackets is necessary. In those
situations, please dispose of the two superfluous U-shaped floor anchoring brackets.
Note: The L-shaped floor anchoring brackets that secured the enclosure to the pallet during
shipment may be used for a stand-alone UPS enclosure to enhance stability, but is not
necessary when baying enclosures together. Instead, the three U-shaped floor anchoring
brackets from the baying kit are used.
1. Remove the side panels from the
enclosure(s) to get access to the holes in
the bottom frame.
Note: Make sure that the enclosures
are level to be able to anchor the enclosures to each other.
2. Position two U-
shaped floor
anchoring
brackets under
one enclosure;
one in each
side.
UPS
XR
Front of enclosure
Front of adjacent
enclosure
U-shaped floor
anchoring
bracket