APC 10-40 KVA 380/400/415 V Power Supply User Manual


 
23Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation
Specifications
Battery voltage and current
Recommended cable sizes
Note: Power terminal lug diameter: minimum 6 mm (0.2 in).
Torque value: 45 lbf-in/7 Nm.
Note: Use Molex lug type or equivalent, and follow the manufacturer’s specifications.
EPO requirements
Torque specification
Torque specification: Isolators: M5 7 Nm (45 lbf-in).
XR Battery Enclosure 30 kVA 40 kVA
Battery voltage (nominal) ± 192 VDC ± 192 VDC
Battery current (at full load) 69.4 A at ± 192 V 87.9A at ± 192V
Max. current (at end of discharge) 86.6 A at ± 154 V 110.1A at ± 154V
If the XR Battery Enclosure is customer-supplied, please refer
to product-specific data.
North America Europe, Middle East, Asia Japan
208/220 V 380/400/415 V 200/208 V
BAT+, N, BAT- 1 AWG 167º F
(75º C) copper wire
BAT+, N, BAT- 50 mm
2
75º C
(167º F) copper wire
BAT+, N, BAT- 50 mm
2
75º C copper
wire.
Use only 8,08-1,3 mm
2
copper wire rated
minimum 250 V.
SELV voltage 24 VDC
Current: 1500 mA