6-10 Command Language
Table 6-1 Transaction Specification Table Continued
T# Name Type Data Field Class Description
38 RunTime Get UDINT E,V,S Total time power has
been applied. Units:
seconds.
39 TableSelect Get/
Set
USINT E,S,V Parameter table
select
Range 0 3
Note: DDC only
supports 2 tables.
Can only be
changed when under
network control
40 AccDecGroup Get/
Set
USINT E,V,S Accel / decel group
select
Range 1 2 Can
only be changed
when under network
control.
41 WatchdogTime Get/
Set
UINT All Network watchdog
timer Get Units:
10mS
0 = disable
2= 20mS minimum
6000= 60S
maximum
Note: resolution
varies among
product classes.
45 FaultStatus Get USINT All Request current fault
condition
0 = No fault
1xx = Current fault
code (See H Series
Fault Message
Description table at
the end of this
section for
description.)
* Indicates initial powerup value.